Charging voltage
Old Sb-Sb:
max 14,5V
(2,42 V per cell)
float 13,2V (2,2Vpc)
Ca-Ca (most batteries up to 110Ah):
16,25V
(2,71 Vpc)
float 13.1V (2.18Vpc)
Gel (old):
14,1V (2,35 Vpc)
float 13,2V (2,2 Vpc)
AGM:
14,9 V (2,48Vpc)
limit/hold: 15,6 (2,6 Vpc)
float: 13,6V (2,27 Vpc)
Sb-Ca (deep discharge / special / over 110Ah):
14.55V (2,43Vpc)
absorption:
16,45
(2,73 Vpc)
float: 13,1V (2,18 Vpc)